0400 MAN Fire Damper

0400 MAN fire damper has been designed to stop the spread of fire through ventilation ducts passing through walls. It will close when reaching a temperature of 72ºC and then remain closed to prevent the spread of fire while maintaining the integrity of the wall. The 0400 series is used in commercial, residential, and healthcare, complying with the harmonised standard BS EN 13501 with UKCA and European CE certification.

The 0400 MAN fire damper has been designed to be installed in reduced space, and is activated with a mechanical fuse thread that melts upon reaching 72ºC releasing the spring-loaded blade closed. The damper is resettable from the outside, which makes it easy to reset. The damper can be held fully open or partially open for volume control.

The minimum damper size is Ø100mm up to a maximum of Ø310mm. The damper has been tested to BS EN 1366-2 in both directions as required in the harmonised standard BS EN 15650 and has a classification for two hours as BS EN 13501-3. The damper has a fixing frame for wall mounting in drywall or blockwork. For damper installation, please refer to the Declaration of Performance and the Installation, Operation & Maintenance instructions that give full details.

Advanced Air also offers training on how to install the products correctly within our in-house training facility. Installation Training

0400 Fire & Smoke Damper Product Brochure

0400 DoP (UK)

0400 CCP (UK)

0400 DoP (EU)

0400 CCP (EU)

0400 Installation Manual

Features

  • Complies with BS EN 15650
  • Tested in both directions to BS EN 1366-2
  • E120 classification to BS EN 13501-3
  • Externally resettable
  • Suitable volume control
  • Easy installation

Tech Specs

  • Blades are double-skinned 1.2mm mild steel with a fire-retardant gasket sandwiched between each blade. Option of 1.2mm 430 Stainless Steel
  • Case 0.9mm galvanised steel
  • Installation frame drywall 1.2mm galvanised steel
  • Shaft 6mm dia 303 stainless steel
  • Case leakage DW144, class C 100 and 125 dia, Class B 150 to 315 dia
  • Blade leakage class 3: 315 dia, class 2: 100 dia to 300 dia
  • Maximum duct velocity: 10 m/s
  • Maximum duct pressure: 10,000 pascals

Dimensions

100mm diameter
125mm diameter
150mm diameter
160mm diameter
200mm diameter
250mm diameter
300mm diameter
315mm diameter