0400 FME Fire & Smoke Damper

0400 FME Fire Damper

Circular fire smoke damper 0400 FME has been designed to stop the spread of fire and smoke through ventilation ducts passing through walls. They close within 16 seconds of receiving an alarm to prevent the spread of cold smoke and remain closed to prevent the spread of fire by maintaining the integrity of the installation. The 0400 series is used in commercial, residential, and healthcare applications in compliance with the harmonised standard BS EN 13501 with UKCA and European CE certification.

The circular 0400 FME has been designed to reduce space and is complete with a spring return actuator and an electrical thermal fuse rated to 72 ºC. Upon reaching this temperature, the thermal fuse cuts the power to the actuator, which will spring close within 15 seconds.

The minimum damper size is Ø100mm up to a maximum of Ø310mm. The damper has been tested to BS EN 1366-2 in both directions as required in the harmonised standard BS EN 15650 and has a classification for 2 hours as BS EN 13501-3. The damper has a fixing frame for wall mounting in drywall or blockwork. For damper installation, please refer to the Declaration of Performance and the Installation, Operation & Maintenance instructions that give full details.

Advanced Air also offers training on how to install the products correctly within our in-house training facility. Installation Training

0400 Fire & Smoke Damper Product Brochure

0400 DoP (UK)

0400 CCP (UK)

0400 DoP (EU)

0400 CCP (EU)

0400 Installation Manual

 

Features

  • Complies with BS EN 15650
  • Tested in both directions to BS EN 1366-2
  • ES 120 classification to BS EN 13501-3
  • 90 sec opening 15 sec closing
  • Suitable volume control
  • Easy Installation.

Tech Specs

  • Blades Double skinned 1.2mm mild steel with a fire retardant gasket sandwiched between each blade: Option of 1.2mm 430 Stainless Steel
  • Case 0.9mm Galvanised Steel
  • Installation Frame Drywall 1.2mm Galvanised Steel
  • Shaft 6mm dia 303 Stainless Steel
  • Case Leakage DW144 Class C 100 & 125dia, Class B 150 to 315dia
  • Blade Leakage Class 3: 315 dia, Class 2: 100 dia to 300 dia
  • Maximum Duct Velocity: 10 m/s
  • Maximum Duct Pressure: 10,000 pascals

Dimensions

100mm diameter
125mm diameter
150mm diameter
160mm diameter
200mm diameter
250mm diameter
300mm diameter
315mm diameter